How MDC Water Measures Up With U.S. EPA and/or Connecticut Standards (2003-2004)

Allowable Limit MDC Analysis Reservoir 6 Finished Water West Hartford
Cadmium 0.05 ppm <0.002 ppm <0.002 ppm
Copper 1.3 ppm 0.016 ppm 0.009 ppm
Fluoride 4.0 ppm 1.02 ppm 0.97 ppm
Iron 0.3 ppm <0.01 ppm 0.02 ppm
Lead 0.015ppm <0.001 ppm <0.001 ppm
Total Triahalomethanes 80 ppb 26.8 ppb 41.4 ppb
Gross Alpha Radioactivity 15 pci/L 0.78 +/­ 0.38 pci/L 1.32 +/­ 0.43 pci/L
Gross Beta Particle Activity 50 pci/L 0.74 +/­ 0.83 pci/L 1.04 +/­ 1.1 pci/L
pH (acidity) 6.4 ­ 8.5 7.8 7.7
Color 15 units 1 unit 3 units
Turbidity 1.0 Nephelometric
Turbidity Unit (NTU)
0.11 NTU 0.25 NTU
Coliform Bacteria <5% < 0.01% < 0.01%
Hardness 150 ppm 17 ppm 33 ppm

Volatile Organic Chemicals Sampling Program: 2003 Results
Chemical MCL (ppb) MDC Representative
Value (ppb)
Total Trihalomethanes 80 35
Haloactetic Acids (5) 60 26
Benzene 5 ND
Carbon Tetrachloride 5 ND
1,2­Dichloroethane 5 ND
Trichloroethylene 5 ND
Para­Dichlorobenzene 75 ND
1, 1-Dichloroethylene 7 ND
1, 1, 1-Trichloroethane 200 ND
Vinyl Chloride 2 ND
Proposed or State of Connecticut  MCL(ppb)
Toluene 1,000 ND
Tetrachloroethylene 5 ND
Styrene 100 ND

ABBREVIATIONS
ppm parts per million
ppb parts per billion
pci/L picocuries/liter
MCL maximum contaminant level
L liter
ND none detected